Transmission line fault location: Simulation of real faults using wavelet transform based travelling wave methods
Abstract
In this study, High Voltage Transmission Line fault location accuracy of distance relays running
impedance algorithm are compared with Travelling Wave (TW) method. Line faults in 154 kV Tatvan –
Muş and 154 kV Patnos-Erciş lines in Turkish Electrical Transmission System are analyzed. Real faults
in both lines are simulated in MATLAB-SIMULINK. Tower configuration and conductor properties of
the lines and the source impedances are included in the simulation to comply with real system. Simulations
show that both single-end and double-end Wavelet Transform (WT) based TW methods have better
accuracy then the distance relays computing fault location by impedance methods.