dc.contributor.author | Akdag, Mustafa | |
dc.contributor.author | Rüstemli, Sabir | |
dc.date.accessioned | 2024-02-05T07:01:55Z | |
dc.date.available | 2024-02-05T07:01:55Z | |
dc.date.issued | 2019 | |
dc.identifier.issn | 2146-7706 | |
dc.identifier.uri | http://dspace.beu.edu.tr:8080/xmlui/handle/123456789/13873 | |
dc.description.abstract | In this study, High Voltage Transmission Line fault location accuracy of distance relays running
impedance algorithm are compared with Travelling Wave (TW) method. Line faults in 154 kV Tatvan –
Muş and 154 kV Patnos-Erciş lines in Turkish Electrical Transmission System are analyzed. Real faults
in both lines are simulated in MATLAB-SIMULINK. Tower configuration and conductor properties of
the lines and the source impedances are included in the simulation to comply with real system. Simulations
show that both single-end and double-end Wavelet Transform (WT) based TW methods have better
accuracy then the distance relays computing fault location by impedance methods. | tr_TR |
dc.language.iso | English | tr_TR |
dc.publisher | Bitlis Eren Üniversitesi | tr_TR |
dc.rights | info:eu-repo/semantics/openAccess | tr_TR |
dc.subject | Fault Location | tr_TR |
dc.subject | Transmission line | tr_TR |
dc.subject | Travelling Wave | tr_TR |
dc.subject | Wavelet Transform | tr_TR |
dc.title | Transmission line fault location: Simulation of real faults using wavelet transform based travelling wave methods | tr_TR |
dc.type | Article | tr_TR |
dc.identifier.issue | 2 | tr_TR |
dc.identifier.startpage | 88 | tr_TR |
dc.identifier.endpage | 97 | tr_TR |
dc.relation.journal | Bitlis Eren University Journal of Science and Technology | tr_TR |
dc.identifier.volume | 9 | tr_TR |