| dc.description.abstract | In this study, High Voltage Transmission Line fault location accuracy of distance relays running
impedance algorithm are compared with Travelling Wave (TW) method. Line faults in 154 kV Tatvan –
Muş and 154 kV Patnos-Erciş lines in Turkish Electrical Transmission System are analyzed. Real faults
in both lines are simulated in MATLAB-SIMULINK. Tower configuration and conductor properties of
the lines and the source impedances are included in the simulation to comply with real system. Simulations
show that both single-end and double-end Wavelet Transform (WT) based TW methods have better
accuracy then the distance relays computing fault location by impedance methods. | tr_TR | 
| dc.language.iso | English | tr_TR | 
| dc.publisher | Bitlis Eren Üniversitesi | tr_TR | 
| dc.rights | info:eu-repo/semantics/openAccess | tr_TR | 
| dc.subject | Fault Location | tr_TR | 
| dc.subject | Transmission line | tr_TR | 
| dc.subject | Travelling Wave | tr_TR | 
| dc.subject | Wavelet Transform | tr_TR | 
| dc.title | Transmission line fault location: Simulation of real faults using wavelet transform based travelling wave methods | tr_TR | 